Borri B9000FXS 60 kVA
Transformer-based 3-phase UPS for HVAC, safety and emergency systems, process plant, machine tools, medical equipment and data centres. Can be customised to the specific process.
- Output transformer with galvanic isolation
- Free layout thanks to the airflow design
- Customisation for process plant
Technical data
| Rating (kVA) | 60 |
| Nominal power (kW) | 54 |
| Dimensions WxDxH (mm) | 815x825x1670 |
| UPS weight (kg) | 570 |
| Battery configuration | External, 300 to 312 cells, VRLA (other options) |
Input
| Connection type | Hardwired 3w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); +10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static ±1%; dynamic: IEC EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | Inverter: 125% for 10 min, 150% for 1 min, 199% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; input terminal block for: remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.. Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, top cable entry; load-sync for single UPS and load-sync box (2 UPS systems); backfeed protection; other options on request |
System
| Protection degree | IP 20 (other options) |
| Colour | RAL 7016 (other options) |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | <1000 m without power reduction, >1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <62 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for B9000FXS.



Borri B9000FXS 80 kVA
Transformer-based 3-phase UPS for HVAC, safety and emergency systems, process plant, machine tools, medical equipment and data centres. Can be customised to the specific process.
- Output transformer with galvanic isolation
- Free layout thanks to the airflow design
- Customisation for process plant
Technical data
| Rating (kVA) | 80 |
| Nominal power (kW) | 72 |
| Dimensions WxDxH (mm) | 815x825x1670 |
| UPS weight (kg) | 600 |
| Battery configuration | External, 300 to 312 cells, VRLA (other options) |
Input
| Connection type | Hardwired 3w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); +10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static ±1%; dynamic: IEC EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | Inverter: 125% for 10 min, 150% for 1 min, 199% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; input terminal block for: remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.. Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, top cable entry; load-sync for single UPS and load-sync box (2 UPS systems); backfeed protection; other options on request |
System
| Protection degree | IP 20 (other options) |
| Colour | RAL 7016 (other options) |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | <1000 m without power reduction, >1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <62 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for B9000FXS.



Borri B9000FXS 100 kVA
Transformer-based 3-phase UPS for HVAC, safety and emergency systems, process plant, machine tools, medical equipment and data centres. Can be customised to the specific process.
- Output transformer with galvanic isolation
- Free layout thanks to the airflow design
- Customisation for process plant
Technical data
| Rating (kVA) | 100 |
| Nominal power (kW) | 90 |
| Dimensions WxDxH (mm) | 815x825x1670 |
| UPS weight (kg) | 625 |
| Battery configuration | External, 300 to 312 cells, VRLA (other options) |
Input
| Connection type | Hardwired 3w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); +10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static ±1%; dynamic: IEC EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | Inverter: 125% for 10 min, 150% for 1 min, 199% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; input terminal block for: remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.. Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, top cable entry; load-sync for single UPS and load-sync box (2 UPS systems); backfeed protection; other options on request |
System
| Protection degree | IP 20 (other options) |
| Colour | RAL 7016 (other options) |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | <1000 m without power reduction, >1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <62 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for B9000FXS.



Borri B9000FXS 125 kVA
Transformer-based 3-phase UPS for HVAC, safety and emergency systems, process plant, machine tools, medical equipment and data centres. Can be customised to the specific process.
- Output transformer with galvanic isolation
- Free layout thanks to the airflow design
- Customisation for process plant
Technical data
| Rating (kVA) | 125 |
| Nominal power (kW) | 112.5 |
| Dimensions WxDxH (mm) | 815x825x1670 |
| UPS weight (kg) | 660 |
| Battery configuration | External, 300 to 312 cells, VRLA (other options) |
Input
| Connection type | Hardwired 3w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); +10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static ±1%; dynamic: IEC EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | Inverter: 125% for 10 min, 150% for 1 min, 199% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; input terminal block for: remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.. Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, top cable entry; load-sync for single UPS and load-sync box (2 UPS systems); backfeed protection; other options on request |
System
| Protection degree | IP 20 (other options) |
| Colour | RAL 7016 (other options) |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | <1000 m without power reduction, >1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <62 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for B9000FXS.



Borri B9000FXS 160 kVA
Transformer-based 3-phase UPS for HVAC, safety and emergency systems, process plant, machine tools, medical equipment and data centres. Can be customised to the specific process.
- Output transformer with galvanic isolation
- Free layout thanks to the airflow design
- Customisation for process plant
Technical data
| Rating (kVA) | 160 |
| Nominal power (kW) | 144 |
| Dimensions WxDxH (mm) | 815x825x1670 |
| UPS weight (kg) | 715 |
| Battery configuration | External, 300 to 312 cells, VRLA (other options) |
Input
| Connection type | Hardwired 3w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); +10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static ±1%; dynamic: IEC EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | Inverter: 125% for 10 min, 150% for 1 min, 199% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; input terminal block for: remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.. Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, top cable entry; load-sync for single UPS and load-sync box (2 UPS systems); backfeed protection; other options on request |
System
| Protection degree | IP 20 (other options) |
| Colour | RAL 7016 (other options) |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | <1000 m without power reduction, >1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <62 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for B9000FXS.



Borri B9000FXS 200 kVA
Transformer-based 3-phase UPS for HVAC, safety and emergency systems, process plant, machine tools, medical equipment and data centres. Can be customised to the specific process.
- Output transformer with galvanic isolation
- Free layout thanks to the airflow design
- Customisation for process plant
Technical data
| Rating (kVA) | 200 |
| Nominal power (kW) | 180 |
| Dimensions WxDxH (mm) | 1217x853x1900 |
| UPS weight (kg) | 970 |
| Battery configuration | External, 300 to 312 cells, VRLA (other options) |
Input
| Connection type | Hardwired 3w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); +10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static ±1%; dynamic: IEC EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | Inverter: 125% for 10 min, 150% for 1 min, 199% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; input terminal block for: remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.. Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, top cable entry; load-sync for single UPS and load-sync box (2 UPS systems); backfeed protection; other options on request |
System
| Protection degree | IP 20 (other options) |
| Colour | RAL 7016 (other options) |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | <1000 m without power reduction, >1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <62 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for B9000FXS.



Borri B9000FXS 250 kVA
Transformer-based 3-phase UPS for HVAC, safety and emergency systems, process plant, machine tools, medical equipment and data centres. Can be customised to the specific process.
- Output transformer with galvanic isolation
- Free layout thanks to the airflow design
- Customisation for process plant
Technical data
| Rating (kVA) | 250 |
| Nominal power (kW) | 225 |
| Dimensions WxDxH (mm) | 1217x853x1900 |
| UPS weight (kg) | 1090 |
| Battery configuration | External, 300 to 312 cells, VRLA (other options) |
Input
| Connection type | Hardwired 3w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); +10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static ±1%; dynamic: IEC EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | Inverter: 125% for 10 min, 150% for 1 min, 199% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; input terminal block for: remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.. Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, top cable entry; load-sync for single UPS and load-sync box (2 UPS systems); backfeed protection; other options on request |
System
| Protection degree | IP 20 (other options) |
| Colour | RAL 7016 (other options) |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | <1000 m without power reduction, >1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <62 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for B9000FXS.



Borri B9000FXS 300 kVA
Transformer-based 3-phase UPS for HVAC, safety and emergency systems, process plant, machine tools, medical equipment and data centres. Can be customised to the specific process.
- Output transformer with galvanic isolation
- Free layout thanks to the airflow design
- Customisation for process plant
Technical data
| Rating (kVA) | 300 |
| Nominal power (kW) | 270 |
| Dimensions WxDxH (mm) | 1217x853x1900 |
| UPS weight (kg) | 1170 |
| Battery configuration | External, 300 to 312 cells, VRLA (other options) |
Input
| Connection type | Hardwired 3w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); +10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static ±1%; dynamic: IEC EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | Inverter: 125% for 10 min, 150% for 1 min, 199% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; input terminal block for: remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.. Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, top cable entry; load-sync for single UPS and load-sync box (2 UPS systems); backfeed protection; other options on request |
System
| Protection degree | IP 20 (other options) |
| Colour | RAL 7016 (other options) |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | <1000 m without power reduction, >1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <62 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |