Borri E2001 4 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 110 Vdc | 5 |
| 220 Vdc | 5 |
| Nominal power kW | 4 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 8 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 110 Vdc | 10 |
| 220 Vdc | 10 |
| Nominal power kW | 8 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 12 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 110 Vdc | 15 |
| 220 Vdc | 15 |
| Nominal power kW | 12 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 16 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 110 Vdc | 20 |
| 220 Vdc | 20 |
| Nominal power kW | 16 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 24 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 110 Vdc | 30 |
| 220 Vdc | 30 |
| Nominal power kW | 24 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 32 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 110 Vdc | 40 |
| 220 Vdc | 40 |
| Nominal power kW | 32 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 40 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 110 Vdc | 50 |
| 220 Vdc | 50 |
| 400 Vdc | 50 |
| Nominal power kW | 40 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 48 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 220 Vdc | 60 |
| 400 Vdc | 60 |
| Nominal power kW | 48 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 64 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 220 Vdc | 80 |
| 400 Vdc | 80 |
| Nominal power kW | 64 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 80 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 220 Vdc | 100 |
| 400 Vdc | 100 |
| Nominal power kW | 80 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 96 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 400 Vdc | 120 |
| Nominal power kW | 96 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 128 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 400 Vdc | 160 |
| Nominal power kW | 128 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.

Borri E2001 160 kW
Online double-conversion industrial UPS with full galvanic isolation and single-phase output, built for harsh environments.
- Full galvanic isolation
- 110, 220 or 400 V DC battery voltage
- Also available as E2001.igbt
Technical data
Rating (kVA)* @ P.F. 0.8 vs DC Rated Vol
| 400 Vdc | 200 |
| Nominal power kW | 160 |
Input
| Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power Factor | From 0,8 up to unity (depending on rectifier technology) |
| Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
| Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
Battery
| DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
| Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Output
| Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
| Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
| Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
| Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms |
System
| Cooling | Forced ventilation (optional redundant fans) |
| Colour | RAL 7035 (optional other colours) |
| Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Environmental
| Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
| Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
User Interface
| Front panel | Graphic display, mimic LED panel, function keys, local EPO |
| Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Standards
| Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE (CSA/UL certified as optional) |
Source: Borri product page for E2001.