Borri · E8031 / E8033 ECS
Borri E8031 / E8033 ECS 10 kVA
Central emergency supply built to EN 50171 for emergency and safety installations such as fire detection, extinguishing, paging and emergency lighting.
10 kVArating
9 kWnominal power
Up to 98%efficiency
450 × 670 × 1200 mmW × D × H
- Complies with EN 50171
- Single- or three-phase output
- Power to EN 50171 stated separately
Price on requestModel: E8031 / E8033 ECS 10 kVA
Technical data
| Rating (kVA) | 10 |
| Nominal power (kW) | 9 |
| Nominal power as per EN 50171 (kW) | 7.5 |
| UPS dimensions WxDxH (mm) | 450x670x1200 |
| UPS weight (kg) | 100 |
| Battery | External, 360 to 372 cells, VRLA (other options) |
Input
| Connection type | 3/1-phase units: hardwired 4w (rectifier), 2w (bypass) 3/3-phase units: hardwired 4w (separate bypass input available on request) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 220/230/240 Vac (3/1-phase bypass) |
| Voltage tolerance | -20%, +15% (rectifier) ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.98 |
| Current distortion (THDi) | <4% |
Output
| Connection type | 3/1-phase units: hardwired 2w 3/3-phase units: hardwired 4w |
| Nominal voltage | 3/1-phase units: 220/230/240 Vac 1-phase 3/3-phase units: 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | 120% continuous; 150% for 10 min; |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; terminal block for battery breaker auxiliary contact. Optional: input terminal block (remote emergency power off, external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.); SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional features | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; load-sync for single UPS; AO+EO mode kit; separate input for rectifier and bypass line (for 3-phase output models); parallel kit; other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 7016 |
| Installation layout | 10 cm wall-gap, side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <52 |
Standards and certifications
| CPSS | EN 50171 |
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |

Borri · E8031 / E8033 ECS
Borri E8031 / E8033 ECS 15 kVA
Central emergency supply built to EN 50171 for emergency and safety installations such as fire detection, extinguishing, paging and emergency lighting.
15 kVArating
13.5 kWnominal power
Up to 98%efficiency
450 × 670 × 1200 mmW × D × H
- Complies with EN 50171
- Single- or three-phase output
- Power to EN 50171 stated separately
Price on requestModel: E8031 / E8033 ECS 15 kVA
Technical data
| Rating (kVA) | 15 |
| Nominal power (kW) | 13.5 |
| Nominal power as per EN 50171 (kW) | 11.3 |
| UPS dimensions WxDxH (mm) | 450x670x1200 |
| UPS weight (kg) | 110 |
| Battery | External, 360 to 372 cells, VRLA (other options) |
Input
| Connection type | 3/1-phase units: hardwired 4w (rectifier), 2w (bypass) 3/3-phase units: hardwired 4w (separate bypass input available on request) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 220/230/240 Vac (3/1-phase bypass) |
| Voltage tolerance | -20%, +15% (rectifier) ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.98 |
| Current distortion (THDi) | <4% |
Output
| Connection type | 3/1-phase units: hardwired 2w 3/3-phase units: hardwired 4w |
| Nominal voltage | 3/1-phase units: 220/230/240 Vac 1-phase 3/3-phase units: 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | 120% continuous; 150% for 10 min; |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; terminal block for battery breaker auxiliary contact. Optional: input terminal block (remote emergency power off, external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.); SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional features | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; load-sync for single UPS; AO+EO mode kit; separate input for rectifier and bypass line (for 3-phase output models); parallel kit; other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 7016 |
| Installation layout | 10 cm wall-gap, side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <52 |
Standards and certifications
| CPSS | EN 50171 |
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |

Borri · E8031 / E8033 ECS
Borri E8031 / E8033 ECS 20 kVA
Central emergency supply built to EN 50171 for emergency and safety installations such as fire detection, extinguishing, paging and emergency lighting.
20 kVArating
18 kWnominal power
Up to 98%efficiency
450 × 670 × 1200 mmW × D × H
- Complies with EN 50171
- Single- or three-phase output
- Power to EN 50171 stated separately
Price on requestModel: E8031 / E8033 ECS 20 kVA
Technical data
| Rating (kVA) | 20 |
| Nominal power (kW) | 18 |
| Nominal power as per EN 50171 (kW) | 15 |
| UPS dimensions WxDxH (mm) | 450x670x1200 |
| UPS weight (kg) | 110 |
| Battery | External, 360 to 372 cells, VRLA (other options) |
Input
| Connection type | 3/1-phase units: hardwired 4w (rectifier), 2w (bypass) 3/3-phase units: hardwired 4w (separate bypass input available on request) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 220/230/240 Vac (3/1-phase bypass) |
| Voltage tolerance | -20%, +15% (rectifier) ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.98 |
| Current distortion (THDi) | <4% |
Output
| Connection type | 3/1-phase units: hardwired 2w 3/3-phase units: hardwired 4w |
| Nominal voltage | 3/1-phase units: 220/230/240 Vac 1-phase 3/3-phase units: 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 0.9, without power derating |
| Overload capacity | 120% continuous; 150% for 10 min; |
| Efficiency (AC/AC) | Up to 98% |
| Classification as per IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included: serial RS232 and USB; terminal block for battery breaker auxiliary contact. Optional: input terminal block (remote emergency power off, external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.); SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional features | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; load-sync for single UPS; AO+EO mode kit; separate input for rectifier and bypass line (for 3-phase output models); parallel kit; other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 7016 |
| Installation layout | 10 cm wall-gap, side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| Operating temperature range | 0°C to +40°C |
| Storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <52 |
Standards and certifications
| CPSS | EN 50171 |
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |