Borri · Ingenio Compact
Borri Ingenio Compact 10 kVA
Transformer-free 3-phase UPS of 10–20 kVA with online double conversion and parallel redundancy. For server rooms, networks and telecoms.
10 kVArating
10 kWnominal power
Up to 98%efficiency
440 × 800 × 800 mmW × D × H
- Input power factor 0.99
- ECO mode
- Common battery for parallel systems
Price on requestModel: Ingenio Compact 10 kVA
Technical data
| Rating (kVA) | 10 |
| Nominal power (kW) | 10 |
| UPS dimensions WxDxH (mm) | 440x800x800 |
| UPS weight (kg) | 75 |
| UPS weight with internal battery (kg) | 150 |
| External battery module dimensions WxDxH (mm) | 550x650x1200 |
| Battery configuration | Internal (standard): 180 cells; external: 156/240 cells |
Input
| Connection type | Hardwired 4w |
| Nominal voltage | 400 Vac 3-phase with neutral |
| Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 70 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Power factor | Up to 1, without power derating |
| Overload capacity | 110% for 60 min, 125% for 10 min, 150% for 1 min |
| Efficiency (AC/AC) | Up to 98% |
| Classification by IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Touch screen display |
| Remote communication | Included: serial RS232; backfeed protection monitoring contact, remote EPO contact. Optional: 2 slots for SNMP adapter, ModBus-RTU, contact relay card |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit; other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | 30 cm wall-gap |
| Accessibility | Positioning casters; bottom cable entry |
Environmental
| UPS operating temperature range | 0°C to +40°C |
| UPS storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <52 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |


Borri · Ingenio Compact
Borri Ingenio Compact 15 kVA
Transformer-free 3-phase UPS of 10–20 kVA with online double conversion and parallel redundancy. For server rooms, networks and telecoms.
15 kVArating
15 kWnominal power
Up to 98%efficiency
440 × 800 × 800 mmW × D × H
- Input power factor 0.99
- ECO mode
- Common battery for parallel systems
Price on requestModel: Ingenio Compact 15 kVA
Technical data
| Rating (kVA) | 15 |
| Nominal power (kW) | 15 |
| UPS dimensions WxDxH (mm) | 440x800x800 |
| UPS weight (kg) | 76 |
| UPS weight with internal battery (kg) | 165 |
| External battery module dimensions WxDxH (mm) | 550x650x1200 |
| Battery configuration | Internal (standard): 216 cells; external: 192/240 cells |
Input
| Connection type | Hardwired 4w |
| Nominal voltage | 400 Vac 3-phase with neutral |
| Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 70 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Power factor | Up to 1, without power derating |
| Overload capacity | 110% for 60 min, 125% for 10 min, 150% for 1 min |
| Efficiency (AC/AC) | Up to 98% |
| Classification by IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Touch screen display |
| Remote communication | Included: serial RS232; backfeed protection monitoring contact, remote EPO contact. Optional: 2 slots for SNMP adapter, ModBus-RTU, contact relay card |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit; other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | 30 cm wall-gap |
| Accessibility | Positioning casters; bottom cable entry |
Environmental
| UPS operating temperature range | 0°C to +40°C |
| UPS storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <52 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |


Borri · Ingenio Compact
Borri Ingenio Compact 20 kVA
Transformer-free 3-phase UPS of 10–20 kVA with online double conversion and parallel redundancy. For server rooms, networks and telecoms.
20 kVArating
20 kWnominal power
Up to 98%efficiency
440 × 800 × 800 mmW × D × H
- Input power factor 0.99
- ECO mode
- Common battery for parallel systems
Price on requestModel: Ingenio Compact 20 kVA
Technical data
| Rating (kVA) | 20 |
| Nominal power (kW) | 20 |
| UPS dimensions WxDxH (mm) | 440x800x800 |
| UPS weight (kg) | 76 |
| UPS weight with internal battery (kg) | 165 |
| External battery module dimensions WxDxH (mm) | 550x650x1200 |
| Battery configuration | Internal (standard): 216 cells; external: 192/240 cells |
Input
| Connection type | Hardwired 4w |
| Nominal voltage | 400 Vac 3-phase with neutral |
| Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 70 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Power factor | Up to 1, without power derating |
| Overload capacity | 110% for 60 min, 125% for 10 min, 150% for 1 min |
| Efficiency (AC/AC) | Up to 98% |
| Classification by IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Touch screen display |
| Remote communication | Included: serial RS232; backfeed protection monitoring contact, remote EPO contact. Optional: 2 slots for SNMP adapter, ModBus-RTU, contact relay card |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit; other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | 30 cm wall-gap |
| Accessibility | Positioning casters; bottom cable entry |
Environmental
| UPS operating temperature range | 0°C to +40°C |
| UPS storage temperature range | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <52 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Other models of Ingenio Compact
Do you have a project or a system that needs service?