Borri Ingenio Plus 30 kVA
Transformer-free 3-phase UPS of 30–160 kVA for server rooms, small and medium data centres, healthcare, finance and industry. Borri’s patented Green Conversion gives high efficiency even at light load.
- Green Conversion for high part-load efficiency
- Input power factor 0.99 and THDi below 3 %
- VRLA, Ni-Cd and Li-ion batteries
Technical data
| Rating (kVA) | 30 |
| Nominal power (kW) | 30 |
| UPS dimensions WxDxH (mm) | 460x650x1230 |
| UPS weight (kg) | 120 |
| UPS weight with int. battery (kg) | 365 |
| Battery configuration | Internal or external, 360 to 372 cells, VRLA (other options) |
| Max autonomy with int. battery 70% load (min) | 11 |
Input
| Connection type | Hardwired 4w / Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +20% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | >0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, without power derating |
| Overload capacity | Inverter: 110% for 10 min, 125% for 5 min, 150% for 30; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 99% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included (30 to 160 kVA): backfeed protection monitoring contact. Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.). Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | 10 cm wall-gap, side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| UPS operating temperature | 0°C to +40°C |
| UPS storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <60 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for Ingenio Plus.



Borri Ingenio Plus 40 kVA
Transformer-free 3-phase UPS of 30–160 kVA for server rooms, small and medium data centres, healthcare, finance and industry. Borri’s patented Green Conversion gives high efficiency even at light load.
- Green Conversion for high part-load efficiency
- Input power factor 0.99 and THDi below 3 %
- VRLA, Ni-Cd and Li-ion batteries
Technical data
| Rating (kVA) | 40 |
| Nominal power (kW) | 40 |
| UPS dimensions WxDxH (mm) | 460x650x1230 |
| UPS weight (kg) | 140 |
| UPS weight with int. battery (kg) | 385 |
| Battery configuration | Internal or external, 360 to 372 cells, VRLA (other options) |
| Max autonomy with int. battery 70% load (min) | 7 |
Input
| Connection type | Hardwired 4w / Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +20% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | >0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, without power derating |
| Overload capacity | Inverter: 110% for 10 min, 125% for 5 min, 150% for 30; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 99% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included (30 to 160 kVA): backfeed protection monitoring contact. Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.). Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | 10 cm wall-gap, side by side installation allowed |
| Accessibility | Front and top access, bottom cable entry |
Environmental
| UPS operating temperature | 0°C to +40°C |
| UPS storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <60 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for Ingenio Plus.



Borri Ingenio Plus 60 kVA
Transformer-free 3-phase UPS of 30–160 kVA for server rooms, small and medium data centres, healthcare, finance and industry. Borri’s patented Green Conversion gives high efficiency even at light load.
- Green Conversion for high part-load efficiency
- Input power factor 0.99 and THDi below 3 %
- VRLA, Ni-Cd and Li-ion batteries
Technical data
| Rating (kVA) | 60 |
| Nominal power (kW) | 60 |
| UPS dimensions WxDxH (mm) | 560x940x1500 |
| UPS weight (kg) | 190 |
| UPS weight with int. battery (kg) | 770 |
| Battery configuration | Internal or external, 360 to 372 cells, VRLA (other options) |
| Max autonomy with int. battery 70% load (min) | 12 |
Input
| Connection type | Hardwired 4w / Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +20% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | >0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, without power derating |
| Overload capacity | Inverter: 110% for 10 min, 125% for 5 min, 150% for 30; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 99% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included (30 to 160 kVA): backfeed protection monitoring contact. Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.). Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall and side by side installation allowed, 80 cm clearance on one side |
| Accessibility | Front and top access, side access (with internal battery) bottom cable entry |
Environmental
| UPS operating temperature | 0°C to +40°C |
| UPS storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <60 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for Ingenio Plus.



Borri Ingenio Plus 80 kVA
Transformer-free 3-phase UPS of 30–160 kVA for server rooms, small and medium data centres, healthcare, finance and industry. Borri’s patented Green Conversion gives high efficiency even at light load.
- Green Conversion for high part-load efficiency
- Input power factor 0.99 and THDi below 3 %
- VRLA, Ni-Cd and Li-ion batteries
Technical data
| Rating (kVA) | 80 |
| Nominal power (kW) | 80 |
| UPS dimensions WxDxH (mm) | 560x940x1500 |
| UPS weight (kg) | 215 |
| UPS weight with int. battery (kg) | 785 |
| Battery configuration | Internal or external, 360 to 372 cells, VRLA (other options) |
| Max autonomy with int. battery 70% load (min) | 8 |
Input
| Connection type | Hardwired 4w / Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +20% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | >0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, without power derating |
| Overload capacity | Inverter: 110% for 10 min, 125% for 5 min, 150% for 30; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 99% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included (30 to 160 kVA): backfeed protection monitoring contact. Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.). Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall and side by side installation allowed, 80 cm clearance on one side |
| Accessibility | Front and top access, side access (with internal battery) bottom cable entry |
Environmental
| UPS operating temperature | 0°C to +40°C |
| UPS storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <60 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for Ingenio Plus.



Borri Ingenio Plus 100 kVA
Transformer-free 3-phase UPS of 30–160 kVA for server rooms, small and medium data centres, healthcare, finance and industry. Borri’s patented Green Conversion gives high efficiency even at light load.
- Green Conversion for high part-load efficiency
- Input power factor 0.99 and THDi below 3 %
- VRLA, Ni-Cd and Li-ion batteries
Technical data
| Rating (kVA) | 100 |
| Nominal power (kW) | 100 |
| UPS dimensions WxDxH (mm) | 560x940x1500 |
| UPS weight (kg) | 280 |
| Battery configuration | External 360 to 372 cells, VRLA (other options) |
Input
| Connection type | Hardwired 4w / Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +20% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | >0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, without power derating |
| Overload capacity | Inverter: 110% for 10 min, 125% for 5 min, 150% for 30; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 99% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included (30 to 160 kVA): backfeed protection monitoring contact. Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.). Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall and side by side installation allowed, 80 cm clearance on one side |
| Accessibility | Front and top access, side access, bottom cable entry |
Environmental
| UPS operating temperature | 0°C to +40°C |
| UPS storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <60 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for Ingenio Plus.



Borri Ingenio Plus 125 kVA
Transformer-free 3-phase UPS of 30–160 kVA for server rooms, small and medium data centres, healthcare, finance and industry. Borri’s patented Green Conversion gives high efficiency even at light load.
- Green Conversion for high part-load efficiency
- Input power factor 0.99 and THDi below 3 %
- VRLA, Ni-Cd and Li-ion batteries
Technical data
| Rating (kVA) | 125 |
| Nominal power (kW) | 125 |
| UPS dimensions WxDxH (mm) | 560x940x1500 |
| UPS weight (kg) | 290 |
| Battery configuration | External 360 to 372 cells, VRLA (other options) |
Input
| Connection type | Hardwired 4w / Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +20% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | >0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, without power derating |
| Overload capacity | Inverter: 110% for 10 min, 125% for 5 min, 150% for 30; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 99% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included (30 to 160 kVA): backfeed protection monitoring contact. Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.). Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall and side by side installation allowed, 80 cm clearance on one side |
| Accessibility | Front and top access, side access, bottom cable entry |
Environmental
| UPS operating temperature | 0°C to +40°C |
| UPS storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <60 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for Ingenio Plus.



Borri Ingenio Plus 160 kVA
Transformer-free 3-phase UPS of 30–160 kVA for server rooms, small and medium data centres, healthcare, finance and industry. Borri’s patented Green Conversion gives high efficiency even at light load.
- Green Conversion for high part-load efficiency
- Input power factor 0.99 and THDi below 3 %
- VRLA, Ni-Cd and Li-ion batteries
Technical data
| Rating (kVA) | 160 |
| Nominal power (kW) | 160 |
| UPS dimensions WxDxH (mm) | 560x940x1500 |
| UPS weight (kg) | 315 |
| Battery configuration | External 360 to 372 cells, VRLA (other options) |
Input
| Connection type | Hardwired 4w / Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +20% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | >0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, without power derating |
| Overload capacity | Inverter: 110% for 10 min, 125% for 5 min, 150% for 30; bypass: 150% continuous, 1000% for 1 cycle |
| Efficiency (AC/AC) | Up to 99% |
| Classification as per IEC EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
| Remote communication | Included (30 to 160 kVA): backfeed protection monitoring contact. Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.). Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
| Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall and side by side installation allowed, 80 cm clearance on one side |
| Accessibility | Front and top access, side access, bottom cable entry |
Environmental
| UPS operating temperature | 0°C to +40°C |
| UPS storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <60 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for Ingenio Plus.