Borri · Ingenio SFC
Borri Ingenio SFC
Static frequency converter that converts 50 Hz to 60 Hz (or vice versa) and to other voltages. IGBT technology with DSP control gives a clean sine wave output.
95% Typicallyefficiency
- 100–2000 kVA at power factor 1
- THDi below 3 %
- Remote monitoring via Ethernet and Modbus TCP/IP
Price on requestModel: Ingenio SFC
Technical data
Utility - Input
| Voltage | 380 – 440 V ± 10% 3P+N (or any voltage with input transformer) |
| Nominal supply frequency | 50 or 60 Hz |
| Frequency tolerance | ± 5 Hz |
| Harmonics | < 3% THDi (at rated load) |
| Power Factor | Unity |
Load - Output
| Capacity rating | 100 kVA to 2000 kVA pf 1 |
| Voltage | 380 – 480 V (or any voltage with output transformer) |
| Frequency | 50 or 60 Hz (consult factory for other frequencies) |
| Voltage harmonics | < 2.5% THDv (linear load) |
| Overload capability | 120% for 10 mins; 150% for 30 seconds |
| Short circuit current limit | 200% for 2 seconds |
| Voltage accuracy | 50 or 60 Hz (consult factory for other frequencies) |
| Frequency accuracy | +/- 0.1% |
Performance
| Efficiency | 95% Typically |
General
| Enclosure IP rating | IP20 Cabinet (higher protection up to IP54 on request) |
| Operating temperature | 0 - 40°C (up to 55°C with derating) |
| Cooling | Forced air |
| Capacity derating with elevation | -1.0 % / 100 m for application above 1000 m, 2000 m maximum |
| Humidity | < 95% non - condensing |
| Noise | < 65 |
Control interface
| Digital inputs (voltage free contacts) | Start; Stop/Reset |
| Digital outputs (relay outputs) | Running (NO); Warning (NO); Fault (NC) |
| Relay output ratings | 230 Vac 1 A |
Standards
| Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4; |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marine classifications (on request) | DV, DNV, GL, ABS, CCS (++) |
| Marking | CE |
Source: Borri product page for Ingenio SFC.
Other models of Ingenio SFC
Do you have a project or a system that needs service?
Send us the load, required autonomy and voltage level – or describe the task. We will come back with a solution sized for your operation.