Borri · Leonardo T
Borri Leonardo T 6 kVA
Online 1-phase tower UPS for networks, servers and small data centres. Can be paralleled redundantly for higher availability.
6 kVArating
5.4 kWnominal power
290 × 645 × 748 mmW × D × H
86 kgweight
- Online double conversion
- Parallel redundant configuration
- 6 and 10 kVA
Price on requestModel: Leonardo T 6 kVA
Technical data
| UPS Type | T* |
| Rating (kVA) | 6 |
| Nominal power (kW) | 5.4 |
| UPS dimensions WxDxH (mm) | 290x645x748 |
| UPS weight (kg) | 86 |
Input
| Connection type | Hardwired 2w (rectifier), 2w (bypass) |
| Nominal voltage | 230 Vac 1-phase |
| Voltage range | 160 to 280 Vac |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <6% |
Output
| Connection type | Hardwired 2w |
| Nominal voltage | 230 Vac +/-1% 1-phase |
| Frequency | 50/60 Hz |
| Power factor | Up to 0.9, without power derating |
| Overload capability | 104% continuous, 150% for 160 seconds, >150% transfer to bypass |
| Mode of operation | On-line, Eco-mode |
| Classification by IEC/EN 62040-3 | VFI-SS-11 |
Battery
| Autonomy time internal battery(min)◆ | 50% load / 25 / 17 |
| 100% load | 9 |
Connectivity and function extensions
| Front panel | Display LCD, status LED, function keys |
| Communication | Included: USB, RS232 card, EPO. Optional: RS485 card, dry contact card, SNMP card. Compatible platforms: Windows, Linux, Mac |
Environmental
| Operating temperature range | 0°C to +40°C |
| Altitude (AMSL) | <1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <50 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Marking | CE |
Source: Borri product page for Leonardo T.


Borri · Leonardo T
Borri Leonardo T 10 kVA
Online 1-phase tower UPS for networks, servers and small data centres. Can be paralleled redundantly for higher availability.
10 kVArating
9 kWnominal power
290 × 645 × 748 mmW × D × H
96 kgweight
- Online double conversion
- Parallel redundant configuration
- 6 and 10 kVA
Price on requestModel: Leonardo T 10 kVA
Technical data
| UPS Type | T* |
| Rating (kVA) | 10 |
| Nominal power (kW) | 9 |
| UPS dimensions WxDxH (mm) | 290x645x748 |
| UPS weight (kg) | 96 |
Input
| Connection type | Hardwired 2w (rectifier), 2w (bypass) |
| Nominal voltage | 230 Vac 1-phase |
| Voltage range | 160 to 280 Vac |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <6% |
Output
| Connection type | Hardwired 2w |
| Nominal voltage | 230 Vac +/-1% 1-phase |
| Frequency | 50/60 Hz |
| Power factor | Up to 0.9, without power derating |
| Overload capability | 104% continuous, 150% for 160 seconds, >150% transfer to bypass |
| Mode of operation | On-line, Eco-mode |
| Classification by IEC/EN 62040-3 | VFI-SS-11 |
Battery
| Autonomy time internal battery(min)◆ | 50% load / 25 / 17 |
| 100% load | 6 |
Connectivity and function extensions
| Front panel | Display LCD, status LED, function keys |
| Communication | Included: USB, RS232 card, EPO. Optional: RS485 card, dry contact card, SNMP card. Compatible platforms: Windows, Linux, Mac |
Environmental
| Operating temperature range | 0°C to +40°C |
| Altitude (AMSL) | <1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 m (dBA) | <50 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Marking | CE |
Source: Borri product page for Leonardo T.