Borri UMB AC07 20 kW
Modular industrial UPS built from 20 kW modules. High efficiency also at part load and short repair time thanks to the modules.
- 20 kW modules (3 × 6.7 kW)
- Efficiency up to 96 % in double conversion
- Short MTTR
Technical data
| Rating (kW) | 20 |
| Module nominal power (kW) | 20 (3x6.7 kW) |
Input
| Input voltage | 380/400/415 Vac 3-phase with neutral |
| Input frequency | 45/65 Hz (auto-sensing or selectable by the User) |
| Input voltage range | 400 V +15%/-20% |
| Power factor | 0.99 |
| Input THDi | <3% |
| Bypass input voltage | 380/400/415 Vac 3-phase ±20% |
Battery
| Nominal voltage | 216 V to 252 V |
| Battery technologies | Maintenance-free Lead Acid (VRLA-AGM) |
| Charging current (A) | 7.5 |
Output
| Nominal voltage | 380/400/415 Vac 3-phase + N +/- 1%; 220/230/240 Vac 1-phase +/- 1% (only 20 kW) |
| Frequency | 50/60 Hz |
| Voltage regulation | ±1% static; dynamic: IEC/EN 62040-3 Class 1 |
| Overload capacity | 115% for 10 min; 135% for 60 sec |
| Harmonic Distortion THDv | <1% linear load; <5% non-linear load |
System
| Dimensions WxDxH (mm) | 600x800x2100 |
| Cooling | Forced ventilation |
| Colour | RAL 7035 (others on option) |
| Protection degree (IEC 60529) | IP 20 (optional up to IP 42) |
| Efficiency (AC/AC) | Up to 96% |
Environmental
| Operating temperature | 0°C to +40°C (derated up to 55°C)/ Storage: 10°C to +70°C |
| Altitude | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 meter (dBA) | 50 to 65 (depending on power rating) |
User Interface
| Front panel | Cabinet graphic display, mimic LED panel and keyboard, local EPO |
| Connectivity | Included: RS232 card, USB. Optional: Modbus-RTU, PROFIBUS DP, MODBUS TCIP |
Standards
| Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UMB AC07.


Borri UMB AC07 40 kW
Modular industrial UPS built from 20 kW modules. High efficiency also at part load and short repair time thanks to the modules.
- 20 kW modules (3 × 6.7 kW)
- Efficiency up to 96 % in double conversion
- Short MTTR
Technical data
| Rating (kW) | 40 |
| Module nominal power (kW) | 20 (3x6.7 kW) |
Input
| Input voltage | 380/400/415 Vac 3-phase with neutral |
| Input frequency | 45/65 Hz (auto-sensing or selectable by the User) |
| Input voltage range | 400 V +15%/-20% |
| Power factor | 0.99 |
| Input THDi | <3% |
| Bypass input voltage | 380/400/415 Vac 3-phase ±20% |
Battery
| Nominal voltage | 216 V to 252 V |
| Battery technologies | Maintenance-free Lead Acid (VRLA-AGM) |
| Charging current (A) | 15 |
Output
| Nominal voltage | 380/400/415 Vac 3-phase + N +/- 1%; 220/230/240 Vac 1-phase +/- 1% (only 20 kW) |
| Frequency | 50/60 Hz |
| Voltage regulation | ±1% static; dynamic: IEC/EN 62040-3 Class 1 |
| Overload capacity | 115% for 10 min; 135% for 60 sec |
| Harmonic Distortion THDv | <1% linear load; <5% non-linear load |
System
| Dimensions WxDxH (mm) | 600x800x2100 |
| Cooling | Forced ventilation |
| Colour | RAL 7035 (others on option) |
| Protection degree (IEC 60529) | IP 20 (optional up to IP 42) |
| Efficiency (AC/AC) | Up to 96% |
Environmental
| Operating temperature | 0°C to +40°C (derated up to 55°C)/ Storage: 10°C to +70°C |
| Altitude | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 meter (dBA) | 50 to 65 (depending on power rating) |
User Interface
| Front panel | Cabinet graphic display, mimic LED panel and keyboard, local EPO |
| Connectivity | Included: RS232 card, USB. Optional: Modbus-RTU, PROFIBUS DP, MODBUS TCIP |
Standards
| Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UMB AC07.


Borri UMB AC07 60 kW
Modular industrial UPS built from 20 kW modules. High efficiency also at part load and short repair time thanks to the modules.
- 20 kW modules (3 × 6.7 kW)
- Efficiency up to 96 % in double conversion
- Short MTTR
Technical data
| Rating (kW) | 60 |
| Module nominal power (kW) | 20 (3x6.7 kW) |
Input
| Input voltage | 380/400/415 Vac 3-phase with neutral |
| Input frequency | 45/65 Hz (auto-sensing or selectable by the User) |
| Input voltage range | 400 V +15%/-20% |
| Power factor | 0.99 |
| Input THDi | <3% |
| Bypass input voltage | 380/400/415 Vac 3-phase ±20% |
Battery
| Nominal voltage | 216 V to 252 V |
| Battery technologies | Maintenance-free Lead Acid (VRLA-AGM) |
| Charging current (A) | 22.5 |
Output
| Nominal voltage | 380/400/415 Vac 3-phase + N +/- 1%; 220/230/240 Vac 1-phase +/- 1% (only 20 kW) |
| Frequency | 50/60 Hz |
| Voltage regulation | ±1% static; dynamic: IEC/EN 62040-3 Class 1 |
| Overload capacity | 115% for 10 min; 135% for 60 sec |
| Harmonic Distortion THDv | <1% linear load; <5% non-linear load |
System
| Dimensions WxDxH (mm) | 600x800x2100 |
| Cooling | Forced ventilation |
| Colour | RAL 7035 (others on option) |
| Protection degree (IEC 60529) | IP 20 (optional up to IP 42) |
| Efficiency (AC/AC) | Up to 96% |
Environmental
| Operating temperature | 0°C to +40°C (derated up to 55°C)/ Storage: 10°C to +70°C |
| Altitude | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 meter (dBA) | 50 to 65 (depending on power rating) |
User Interface
| Front panel | Cabinet graphic display, mimic LED panel and keyboard, local EPO |
| Connectivity | Included: RS232 card, USB. Optional: Modbus-RTU, PROFIBUS DP, MODBUS TCIP |
Standards
| Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UMB AC07.


Borri UMB AC07 80 kW
Modular industrial UPS built from 20 kW modules. High efficiency also at part load and short repair time thanks to the modules.
- 20 kW modules (3 × 6.7 kW)
- Efficiency up to 96 % in double conversion
- Short MTTR
Technical data
| Rating (kW) | 80 |
| Module nominal power (kW) | 20 (3x6.7 kW) |
Input
| Input voltage | 380/400/415 Vac 3-phase with neutral |
| Input frequency | 45/65 Hz (auto-sensing or selectable by the User) |
| Input voltage range | 400 V +15%/-20% |
| Power factor | 0.99 |
| Input THDi | <3% |
| Bypass input voltage | 380/400/415 Vac 3-phase ±20% |
Battery
| Nominal voltage | 216 V to 252 V |
| Battery technologies | Maintenance-free Lead Acid (VRLA-AGM) |
| Charging current (A) | 30 |
Output
| Nominal voltage | 380/400/415 Vac 3-phase + N +/- 1%; 220/230/240 Vac 1-phase +/- 1% (only 20 kW) |
| Frequency | 50/60 Hz |
| Voltage regulation | ±1% static; dynamic: IEC/EN 62040-3 Class 1 |
| Overload capacity | 115% for 10 min; 135% for 60 sec |
| Harmonic Distortion THDv | <1% linear load; <5% non-linear load |
System
| Dimensions WxDxH (mm) | 600x800x2100 |
| Cooling | Forced ventilation |
| Colour | RAL 7035 (others on option) |
| Protection degree (IEC 60529) | IP 20 (optional up to IP 42) |
| Efficiency (AC/AC) | Up to 96% |
Environmental
| Operating temperature | 0°C to +40°C (derated up to 55°C)/ Storage: 10°C to +70°C |
| Altitude | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 meter (dBA) | 50 to 65 (depending on power rating) |
User Interface
| Front panel | Cabinet graphic display, mimic LED panel and keyboard, local EPO |
| Connectivity | Included: RS232 card, USB. Optional: Modbus-RTU, PROFIBUS DP, MODBUS TCIP |
Standards
| Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UMB AC07.


Borri UMB AC07 100 kW
Modular industrial UPS built from 20 kW modules. High efficiency also at part load and short repair time thanks to the modules.
- 20 kW modules (3 × 6.7 kW)
- Efficiency up to 96 % in double conversion
- Short MTTR
Technical data
| Rating (kW) | 100 |
| Module nominal power (kW) | 20 (3x6.7 kW) |
Input
| Input voltage | 380/400/415 Vac 3-phase with neutral |
| Input frequency | 45/65 Hz (auto-sensing or selectable by the User) |
| Input voltage range | 400 V +15%/-20% |
| Power factor | 0.99 |
| Input THDi | <3% |
| Bypass input voltage | 380/400/415 Vac 3-phase ±20% |
Battery
| Nominal voltage | 216 V to 252 V |
| Battery technologies | Maintenance-free Lead Acid (VRLA-AGM) |
| Charging current (A) | 37.5 |
Output
| Nominal voltage | 380/400/415 Vac 3-phase + N +/- 1%; 220/230/240 Vac 1-phase +/- 1% (only 20 kW) |
| Frequency | 50/60 Hz |
| Voltage regulation | ±1% static; dynamic: IEC/EN 62040-3 Class 1 |
| Overload capacity | 115% for 10 min; 135% for 60 sec |
| Harmonic Distortion THDv | <1% linear load; <5% non-linear load |
System
| Dimensions WxDxH (mm) | 1200x800x2100 |
| Cooling | Forced ventilation |
| Colour | RAL 7035 (others on option) |
| Protection degree (IEC 60529) | IP 20 (optional up to IP 42) |
| Efficiency (AC/AC) | Up to 96% |
Environmental
| Operating temperature | 0°C to +40°C (derated up to 55°C)/ Storage: 10°C to +70°C |
| Altitude | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 meter (dBA) | 50 to 65 (depending on power rating) |
User Interface
| Front panel | Cabinet graphic display, mimic LED panel and keyboard, local EPO |
| Connectivity | Included: RS232 card, USB. Optional: Modbus-RTU, PROFIBUS DP, MODBUS TCIP |
Standards
| Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UMB AC07.


Borri UMB AC07 120 kW
Modular industrial UPS built from 20 kW modules. High efficiency also at part load and short repair time thanks to the modules.
- 20 kW modules (3 × 6.7 kW)
- Efficiency up to 96 % in double conversion
- Short MTTR
Technical data
| Rating (kW) | 120 |
| Module nominal power (kW) | 20 (3x6.7 kW) |
Input
| Input voltage | 380/400/415 Vac 3-phase with neutral |
| Input frequency | 45/65 Hz (auto-sensing or selectable by the User) |
| Input voltage range | 400 V +15%/-20% |
| Power factor | 0.99 |
| Input THDi | <3% |
| Bypass input voltage | 380/400/415 Vac 3-phase ±20% |
Battery
| Nominal voltage | 216 V to 252 V |
| Battery technologies | Maintenance-free Lead Acid (VRLA-AGM) |
| Charging current (A) | 45 |
Output
| Nominal voltage | 380/400/415 Vac 3-phase + N +/- 1%; 220/230/240 Vac 1-phase +/- 1% (only 20 kW) |
| Frequency | 50/60 Hz |
| Voltage regulation | ±1% static; dynamic: IEC/EN 62040-3 Class 1 |
| Overload capacity | 115% for 10 min; 135% for 60 sec |
| Harmonic Distortion THDv | <1% linear load; <5% non-linear load |
System
| Dimensions WxDxH (mm) | 1200x800x2100 |
| Cooling | Forced ventilation |
| Colour | RAL 7035 (others on option) |
| Protection degree (IEC 60529) | IP 20 (optional up to IP 42) |
| Efficiency (AC/AC) | Up to 96% |
Environmental
| Operating temperature | 0°C to +40°C (derated up to 55°C)/ Storage: 10°C to +70°C |
| Altitude | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1 meter (dBA) | 50 to 65 (depending on power rating) |
User Interface
| Front panel | Cabinet graphic display, mimic LED panel and keyboard, local EPO |
| Connectivity | Included: RS232 card, USB. Optional: Modbus-RTU, PROFIBUS DP, MODBUS TCIP |
Standards
| Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
| Safety | IEC EN 62040-1 |
| EMC | IEC EN 62040-2 |
| Environmental aspects | IEC EN 62040-4 |
| Test and performance | IEC EN 62040-3 VFI-SS-111 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UMB AC07.
Other models of UMB AC07
Do you have a project or a system that needs service?
Send us the load, required autonomy and voltage level – or describe the task. We will come back with a solution sized for your operation.