Borri UMB DC 24 V
Modular DC UPS system for oil & gas, power generation, utilities, water treatment, transport, telecoms and process control. Very short repair time thanks to the modules.
- 24–220 V DC
- Compact 19" design
- Short MTTR
Technical data
| DC System Voltage (V) | 24 |
| Module rating (A) | 75 |
| Max Standard rating (A) | 1500 |
Input
| Input voltage | 220/230/240 Vac 1-phase ±10%, / 380/400/415 Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power factor/Input THDi | 0,99 @ 50% - 100% Load / THDi < 5% @ 100% Load |
Output
| DC Voltage range (V) | 21.7–28.8 |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
System
| Cooling | Forced cooled modules |
| Colour | RAL 7035 (others on request) |
| Protection degree (IEC 60529) | IP 20 standard (optional up to IP 54) |
| Output Ripple | < 2% @ Full Load |
| Efficiency | > 92% @ Full Load |
| Options | LED mimic. Customizable status and alarms LED set |
Environmental
| Operating temperature | -10 °C ÷ +40 °C (optional up to 55°C with derating) / Storage temperature: -20 °C ÷ +70 °C |
| Altitude | < 2000 m (derating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | ≤ 65 |
User Interface
| Front panel | LCD display, keyboard |
Standards
| Test and performance | IEC EN 60146-1-1 |
Source: Borri product page for UMB DC.


Borri UMB DC 48 V
Modular DC UPS system for oil & gas, power generation, utilities, water treatment, transport, telecoms and process control. Very short repair time thanks to the modules.
- 24–220 V DC
- Compact 19" design
- Short MTTR
Technical data
| DC System Voltage (V) | 48 |
| Module rating (A) | 42/62.5 |
| Max Standard rating (A) | 840/1250 |
Input
| Input voltage | 220/230/240 Vac 1-phase ±10%, / 380/400/415 Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power factor/Input THDi | 0,99 @ 50% - 100% Load / THDi < 5% @ 100% Load |
Output
| DC Voltage range (V) | 7.6 |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
System
| Cooling | Forced cooled modules |
| Colour | RAL 7035 (others on request) |
| Protection degree (IEC 60529) | IP 20 standard (optional up to IP 54) |
| Output Ripple | < 2% @ Full Load |
| Efficiency | > 92% @ Full Load |
| Options | LED mimic. Customizable status and alarms LED set |
Environmental
| Operating temperature | -10 °C ÷ +40 °C (optional up to 55°C with derating) / Storage temperature: -20 °C ÷ +70 °C |
| Altitude | < 2000 m (derating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | ≤ 65 |
User Interface
| Front panel | LCD display, keyboard |
Standards
| Test and performance | IEC EN 60146-1-1 |
Source: Borri product page for UMB DC.


Borri UMB DC 60 V
Modular DC UPS system for oil & gas, power generation, utilities, water treatment, transport, telecoms and process control. Very short repair time thanks to the modules.
- 24–220 V DC
- Compact 19" design
- Short MTTR
Technical data
| DC System Voltage (V) | 60 |
| Module rating (A) | 42 |
| Max Standard rating (A) | 840 |
Input
| Input voltage | 220/230/240 Vac 1-phase ±10%, / 380/400/415 Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power factor/Input THDi | 0,99 @ 50% - 100% Load / THDi < 5% @ 100% Load |
Output
| DC Voltage range (V) | 54-72 |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
System
| Cooling | Forced cooled modules |
| Colour | RAL 7035 (others on request) |
| Protection degree (IEC 60529) | IP 20 standard (optional up to IP 54) |
| Output Ripple | < 2% @ Full Load |
| Efficiency | > 92% @ Full Load |
| Options | LED mimic. Customizable status and alarms LED set |
Environmental
| Operating temperature | -10 °C ÷ +40 °C (optional up to 55°C with derating) / Storage temperature: -20 °C ÷ +70 °C |
| Altitude | < 2000 m (derating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | ≤ 65 |
User Interface
| Front panel | LCD display, keyboard |
Standards
| Test and performance | IEC EN 60146-1-1 |
Source: Borri product page for UMB DC.


Borri UMB DC 110 V
Modular DC UPS system for oil & gas, power generation, utilities, water treatment, transport, telecoms and process control. Very short repair time thanks to the modules.
- 24–220 V DC
- Compact 19" design
- Short MTTR
Technical data
| DC System Voltage (V) | 110 |
| Module rating (A) | 20 |
| Max Standard rating (A) | 400 |
Input
| Input voltage | 220/230/240 Vac 1-phase ±10%, / 380/400/415 Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power factor/Input THDi | 0,99 @ 50% - 100% Load / THDi < 5% @ 100% Load |
Output
| DC Voltage range (V) | 89.2-171.6 |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
System
| Cooling | Forced cooled modules |
| Colour | RAL 7035 (others on request) |
| Protection degree (IEC 60529) | IP 20 standard (optional up to IP 54) |
| Output Ripple | < 1% @ Full Load |
| Efficiency | > 94% @ Full Load |
| Options | LED mimic. Customizable status and alarms LED set |
Environmental
| Operating temperature | -10 °C ÷ +40 °C (optional up to 55°C with derating) / Storage temperature: -20 °C ÷ +70 °C |
| Altitude | < 2000 m (derating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | ≤ 65 |
User Interface
| Front panel | LCD display, keyboard |
Standards
| Test and performance | IEC EN 60146-1-1 |
Source: Borri product page for UMB DC.


Borri UMB DC 125 V
Modular DC UPS system for oil & gas, power generation, utilities, water treatment, transport, telecoms and process control. Very short repair time thanks to the modules.
- 24–220 V DC
- Compact 19" design
- Short MTTR
Technical data
| DC System Voltage (V) | 125 |
| Module rating (A) | 20 |
| Max Standard rating (A) | 400 |
Input
| Input voltage | 220/230/240 Vac 1-phase ±10%, / 380/400/415 Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power factor/Input THDi | 0,99 @ 50% - 100% Load / THDi < 5% @ 100% Load |
Output
| DC Voltage range (V) | 89.2-171.6 |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
System
| Cooling | Forced cooled modules |
| Colour | RAL 7035 (others on request) |
| Protection degree (IEC 60529) | IP 20 standard (optional up to IP 54) |
| Output Ripple | < 1% @ Full Load |
| Efficiency | > 94% @ Full Load |
| Options | LED mimic. Customizable status and alarms LED set |
Environmental
| Operating temperature | -10 °C ÷ +40 °C (optional up to 55°C with derating) / Storage temperature: -20 °C ÷ +70 °C |
| Altitude | < 2000 m (derating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | ≤ 65 |
User Interface
| Front panel | LCD display, keyboard |
Standards
| Test and performance | IEC EN 60146-1-1 |
Source: Borri product page for UMB DC.


Borri UMB DC 220 V
Modular DC UPS system for oil & gas, power generation, utilities, water treatment, transport, telecoms and process control. Very short repair time thanks to the modules.
- 24–220 V DC
- Compact 19" design
- Short MTTR
Technical data
| DC System Voltage (V) | 220 |
| Module rating (A) | 10 |
| Max Standard rating (A) | 200 |
Input
| Input voltage | 220/230/240 Vac 1-phase ±10%, / 380/400/415 Vac 3-phase ±10%, 50/60 Hz ±10% |
| Power factor/Input THDi | 0,99 @ 50% - 100% Load / THDi < 5% @ 100% Load |
Output
| DC Voltage range (V) | 178.5-297 |
| Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
System
| Cooling | Forced cooled modules |
| Colour | RAL 7035 (others on request) |
| Protection degree (IEC 60529) | IP 20 standard (optional up to IP 54) |
| Output Ripple | < 1% @ Full Load |
| Efficiency | > 94% @ Full Load |
| Options | LED mimic. Customizable status and alarms LED set |
Environmental
| Operating temperature | -10 °C ÷ +40 °C (optional up to 55°C with derating) / Storage temperature: -20 °C ÷ +70 °C |
| Altitude | < 2000 m (derating according to EN 62040-3) |
| Audible noise at 1 meter (dBA) | ≤ 65 |
User Interface
| Front panel | LCD display, keyboard |
Standards
| Test and performance | IEC EN 60146-1-1 |
Source: Borri product page for UMB DC.
Other models of UMB DC
Do you have a project or a system that needs service?
Send us the load, required autonomy and voltage level – or describe the task. We will come back with a solution sized for your operation.