Borri UPSaver 3vo 670 kVA
Modular high-power UPS for large and hyperscale data centres. The system grows with power modules, and maintenance can be done without going to bypass. Up to 21 MW in one system.
- 2–8 power modules per system
- Operating modes: VFI, ECO (VFD) and Ultra High Efficiency
- Service without transfer to bypass
Technical data
| Rating (kVA) | 670 |
| N nominal power (kW) | 670 |
| No. of modules | 2 |
| UPS dimensions WxDxH (mm) | 3800x 970x 2150 |
| UPS weight (kg) | 2140 |
| Battery configuration | External 360 to 372 cells, VRLA, Li-Ion (other options) |
| Connection type | Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier), 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, with no power derating |
| Overload capability | Inverter: 105% continuous at 30° C, 125% for 10 min, 150% for 1 min; bypass: 110% continuous, 150% for 1 min, 700% for 100 ms, 1000% for 10 ms |
| AC/AC efficiency | Up to 99% |
| Classification as per IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | 10” colour touch screen display, 1024x600 pixels |
| Remote communication | Included: serial RS232; input terminal block (remote emergency power off, battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont., external output circuit breaker aux. cont., remote transfer to bypass mode); SPDT contact relay board; ModBus-RTU (RS485); Optional: ModBus-TCP/IP (Ethernet) |
| Optional features | Isolation transformer; battery cabinets; DC protection cabinets; battery thermal probe; parallel kit; load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom and top cable entry |
| Parallel configuration | Up to 8 UPS, for a total of 21 MW |
Environmental
| Operating temperature | 0°C to +40°C with no power derating |
| Storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1m (dBA) | <65 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4; ISO 14025 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UPSaver 3vo.



Borri UPSaver 3vo 1000 kVA
Modular high-power UPS for large and hyperscale data centres. The system grows with power modules, and maintenance can be done without going to bypass. Up to 21 MW in one system.
- 2–8 power modules per system
- Operating modes: VFI, ECO (VFD) and Ultra High Efficiency
- Service without transfer to bypass
Technical data
| Rating (kVA) | 1000 |
| N nominal power (kW) | 1000 |
| No. of modules | 3 |
| UPS dimensions WxDxH (mm) | 4450x 970x 2150 |
| UPS weight (kg) | 2710 |
| Battery configuration | External 360 to 372 cells, VRLA, Li-Ion (other options) |
| Connection type | Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier), 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, with no power derating |
| Overload capability | Inverter: 105% continuous at 30° C, 125% for 10 min, 150% for 1 min; bypass: 110% continuous, 150% for 1 min, 700% for 100 ms, 1000% for 10 ms |
| AC/AC efficiency | Up to 99% |
| Classification as per IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | 10” colour touch screen display, 1024x600 pixels |
| Remote communication | Included: serial RS232; input terminal block (remote emergency power off, battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont., external output circuit breaker aux. cont., remote transfer to bypass mode); SPDT contact relay board; ModBus-RTU (RS485); Optional: ModBus-TCP/IP (Ethernet) |
| Optional features | Isolation transformer; battery cabinets; DC protection cabinets; battery thermal probe; parallel kit; load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom and top cable entry |
| Parallel configuration | Up to 8 UPS, for a total of 21 MW |
Environmental
| Operating temperature | 0°C to +40°C with no power derating |
| Storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1m (dBA) | <65 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4; ISO 14025 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UPSaver 3vo.



Borri UPSaver 3vo 1340 kVA
Modular high-power UPS for large and hyperscale data centres. The system grows with power modules, and maintenance can be done without going to bypass. Up to 21 MW in one system.
- 2–8 power modules per system
- Operating modes: VFI, ECO (VFD) and Ultra High Efficiency
- Service without transfer to bypass
Technical data
| Rating (kVA) | 1340 |
| N nominal power (kW) | 1340 |
| No. of modules | 4 |
| UPS dimensions WxDxH (mm) | 6550x 970x 2150 |
| UPS weight (kg) | 4205 |
| Battery configuration | External 360 to 372 cells, VRLA, Li-Ion (other options) |
| Connection type | Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier), 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, with no power derating |
| Overload capability | Inverter: 105% continuous at 30° C, 125% for 10 min, 150% for 1 min; bypass: 110% continuous, 150% for 1 min, 700% for 100 ms, 1000% for 10 ms |
| AC/AC efficiency | Up to 99% |
| Classification as per IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | 10” colour touch screen display, 1024x600 pixels |
| Remote communication | Included: serial RS232; input terminal block (remote emergency power off, battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont., external output circuit breaker aux. cont., remote transfer to bypass mode); SPDT contact relay board; ModBus-RTU (RS485); Optional: ModBus-TCP/IP (Ethernet) |
| Optional features | Isolation transformer; battery cabinets; DC protection cabinets; battery thermal probe; parallel kit; load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom and top cable entry |
| Parallel configuration | Up to 8 UPS, for a total of 21 MW |
Environmental
| Operating temperature | 0°C to +40°C with no power derating |
| Storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1m (dBA) | <65 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4; ISO 14025 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UPSaver 3vo.



Borri UPSaver 3vo 1670 kVA
Modular high-power UPS for large and hyperscale data centres. The system grows with power modules, and maintenance can be done without going to bypass. Up to 21 MW in one system.
- 2–8 power modules per system
- Operating modes: VFI, ECO (VFD) and Ultra High Efficiency
- Service without transfer to bypass
Technical data
| Rating (kVA) | 1670 |
| N nominal power (kW) | 1670 |
| No. of modules | 5 |
| UPS dimensions WxDxH (mm) | 7200x 970x 2150 |
| UPS weight (kg) | 4775 |
| Battery configuration | External 360 to 372 cells, VRLA, Li-Ion (other options) |
| Connection type | Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier), 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, with no power derating |
| Overload capability | Inverter: 105% continuous at 30° C, 125% for 10 min, 150% for 1 min; bypass: 110% continuous, 150% for 1 min, 700% for 100 ms, 1000% for 10 ms |
| AC/AC efficiency | Up to 99% |
| Classification as per IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | 10” colour touch screen display, 1024x600 pixels |
| Remote communication | Included: serial RS232; input terminal block (remote emergency power off, battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont., external output circuit breaker aux. cont., remote transfer to bypass mode); SPDT contact relay board; ModBus-RTU (RS485); Optional: ModBus-TCP/IP (Ethernet) |
| Optional features | Isolation transformer; battery cabinets; DC protection cabinets; battery thermal probe; parallel kit; load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom and top cable entry |
| Parallel configuration | Up to 8 UPS, for a total of 21 MW |
Environmental
| Operating temperature | 0°C to +40°C with no power derating |
| Storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1m (dBA) | <65 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4; ISO 14025 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UPSaver 3vo.



Borri UPSaver 3vo 2000 kVA
Modular high-power UPS for large and hyperscale data centres. The system grows with power modules, and maintenance can be done without going to bypass. Up to 21 MW in one system.
- 2–8 power modules per system
- Operating modes: VFI, ECO (VFD) and Ultra High Efficiency
- Service without transfer to bypass
Technical data
| Rating (kVA) | 2000 |
| N nominal power (kW) | 2000 |
| No. of modules | 6 |
| UPS dimensions WxDxH (mm) | 7650x 1200x 2150 |
| UPS weight (kg) | 5770 |
| Battery configuration | External 360 to 372 cells, VRLA, Li-Ion (other options) |
| Connection type | Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier), 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, with no power derating |
| Overload capability | Inverter: 105% continuous at 30° C, 125% for 10 min, 150% for 1 min; bypass: 110% continuous, 150% for 1 min, 700% for 100 ms, 1000% for 10 ms |
| AC/AC efficiency | Up to 99% |
| Classification as per IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | 10” colour touch screen display, 1024x600 pixels |
| Remote communication | Included: serial RS232; input terminal block (remote emergency power off, battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont., external output circuit breaker aux. cont., remote transfer to bypass mode); SPDT contact relay board; ModBus-RTU (RS485); Optional: ModBus-TCP/IP (Ethernet) |
| Optional features | Isolation transformer; battery cabinets; DC protection cabinets; battery thermal probe; parallel kit; load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom and top cable entry |
| Parallel configuration | Up to 8 UPS, for a total of 21 MW |
Environmental
| Operating temperature | 0°C to +40°C with no power derating |
| Storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1m (dBA) | <65 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4; ISO 14025 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UPSaver 3vo.



Borri UPSaver 3vo 2340 kVA
Modular high-power UPS for large and hyperscale data centres. The system grows with power modules, and maintenance can be done without going to bypass. Up to 21 MW in one system.
- 2–8 power modules per system
- Operating modes: VFI, ECO (VFD) and Ultra High Efficiency
- Service without transfer to bypass
Technical data
| Rating (kVA) | 2340 |
| N nominal power (kW) | 2340 |
| No. of modules | 7 |
| UPS dimensions WxDxH (mm) | 8800x 1200x 2150 |
| UPS weight (kg) | 6630 |
| Battery configuration | External 360 to 372 cells, VRLA, Li-Ion (other options) |
| Connection type | Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier), 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, with no power derating |
| Overload capability | Inverter: 105% continuous at 30° C, 125% for 10 min, 150% for 1 min; bypass: 110% continuous, 150% for 1 min, 700% for 100 ms, 1000% for 10 ms |
| AC/AC efficiency | Up to 99% |
| Classification as per IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | 10” colour touch screen display, 1024x600 pixels |
| Remote communication | Included: serial RS232; input terminal block (remote emergency power off, battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont., external output circuit breaker aux. cont., remote transfer to bypass mode); SPDT contact relay board; ModBus-RTU (RS485); Optional: ModBus-TCP/IP (Ethernet) |
| Optional features | Isolation transformer; battery cabinets; DC protection cabinets; battery thermal probe; parallel kit; load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom and top cable entry |
| Parallel configuration | Up to 8 UPS, for a total of 21 MW |
Environmental
| Operating temperature | 0°C to +40°C with no power derating |
| Storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1m (dBA) | <65 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4; ISO 14025 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UPSaver 3vo.



Borri UPSaver 3vo 2670 kVA
Modular high-power UPS for large and hyperscale data centres. The system grows with power modules, and maintenance can be done without going to bypass. Up to 21 MW in one system.
- 2–8 power modules per system
- Operating modes: VFI, ECO (VFD) and Ultra High Efficiency
- Service without transfer to bypass
Technical data
| Rating (kVA) | 2670 |
| N nominal power (kW) | 2670 |
| No. of modules | 8 |
| UPS dimensions WxDxH (mm) | (***) |
| UPS weight (kg) | (***) |
| Battery configuration | External 360 to 372 cells, VRLA, Li-Ion (other options) |
| Connection type | Hardwired 4w (rectifier), 4w (bypass) |
| Nominal voltage | 400 Vac 3-phase with neutral (rectifier), 380/400/415 Vac 3-phase with neutral (bypass) |
| Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) |
| Frequency and range | 50/60 Hz, 45 to 65 Hz |
| Power factor | 0.99 |
| Current distortion (THDi) | <3% |
Output
| Connection type | Hardwired 4w |
| Nominal voltage | 380/400/415 Vac 3-phase with neutral |
| Frequency | 50/60 Hz |
| Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
| Power factor | Up to 1, with no power derating |
| Overload capability | Inverter: 105% continuous at 30° C, 125% for 10 min, 150% for 1 min; bypass: 110% continuous, 150% for 1 min, 700% for 100 ms, 1000% for 10 ms |
| AC/AC efficiency | Up to 99% |
| Classification as per IEC/EN 62040-3 | VFI-SS-11 |
Connectivity and function extensions
| Front panel | 10” colour touch screen display, 1024x600 pixels |
| Remote communication | Included: serial RS232; input terminal block (remote emergency power off, battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont., external output circuit breaker aux. cont., remote transfer to bypass mode); SPDT contact relay board; ModBus-RTU (RS485); Optional: ModBus-TCP/IP (Ethernet) |
| Optional features | Isolation transformer; battery cabinets; DC protection cabinets; battery thermal probe; parallel kit; load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
| Protection degree | IP 20 |
| Colour | RAL 9005 |
| Installation layout | Wall, back to back and side by side installation allowed |
| Accessibility | Front and top access, bottom and top cable entry |
| Parallel configuration | Up to 8 UPS, for a total of 21 MW |
Environmental
| Operating temperature | 0°C to +40°C with no power derating |
| Storage temperature | -10°C to +70°C |
| Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
| Audible noise at 1m (dBA) | <65 |
Standards and certifications
| Quality assurance, environment, health and safety | ISO 9001, ISO 14001, ISO 45001 |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Environmental aspects | IEC/EN 62040-4; ISO 14025 |
| Test and performance | IEC/EN 62040-3 |
| Protection degree | IEC 60529 |
| Marking | CE |
Source: Borri product page for UPSaver 3vo.