Active Power CLEANSOURCE® PLUS SMS
CLEANSOURCE® PLUS SMS is Active Power's stand-alone single-module system. It succeeds the CleanSource 300 Norwerk showed previously and is used where one or a few parallel modules cover the need.
- Mid-size data centres and server rooms
- Industry and broadcast
- Healthcare (seismic certified in the US)
Technical data
| Manufacturer | Active Power (Piller) |
| Type | Flywheel UPS |
| Power | 300 kW @ 380/400/415 V 50 Hz |
| Parallel | Up to 2667 kW |
| Efficiency | Up to 98 % |
| Ride-through | Up to 2 minutes (configuration dependent) |
| Ambient | Up to 40 °C |
Source: www.activepower.com.
Technology
How it works
The flywheel stores the energy and a fault-tolerant IGBT architecture protects the load. The energy is sufficient for diesel starting and synchronisation – also when gensets are paralleled.
Without batteries, space and weight are saved, site testing is simplified and there is no routine replacement after a few years.

Application
Where it fits
- Mid-size data centres and server rooms
- Industry and broadcast
- Healthcare (seismic certified in the US)
Versions and options
- Parallel up to 2667 kW
- CSView and BMS integration

Service
Operation and maintenance
Same service concept as the rest of the CleanSource family: annual check-up, bearing changes at fixed intervals and no batteries to replace.
A rotary plant should always be load-tested at commissioning – stepped load, utility failures and transfer to engine.

Other models from Piller
Read more at Bluecircle
Norwerk’s partner Bluecircle has in-depth pages on the topic.
Do you have a project or a system that needs service?
Send us the load, required autonomy and voltage level – or describe the task. We will come back with a solution sized for your operation.