CLEANSOURCE® XT
Active Power (Piller) · Flywheel UPS

Active Power CLEANSOURCE® XT

CLEANSOURCE® XT comes as a single module (SMS) and as a modular system (MMS). The MMS version was introduced as an extended run-time system for data centres and process industry.

225 kW (SMS) / 225–1800 kW (MMS) @ 50 Hzpower
6.2 MJ per flywheelenergy
Up to 98 %efficiency
Up to 2 minutes (load dependent)ride-through
  • Data centres and process industry
  • Sites wanting longer ride-through without batteries
Price on requestRange: 225–1800 kW (50 Hz) / 250–2000 kW (60 Hz)

Technical data

ManufacturerActive Power (Piller)
TypeFlywheel UPS
Power225 kW (SMS) / 225–1800 kW (MMS) @ 50 Hz
Energy6.2 MJ per flywheel
EfficiencyUp to 98 %
Ride-throughUp to 2 minutes (load dependent)
Ambient0–40 °C

Source: www.activepower.com; www.activepower.com.

Technology

How it works

Each flywheel stores 6.2 MJ and provides up to 2 minutes of run time depending on load – ample for diesel start and synchronisation.

The system is built from 225 kW modules (50 Hz) and expands up to 1800 kW.

CLEANSOURCE® XT

Application

Where it fits

  • Data centres and process industry
  • Sites wanting longer ride-through without batteries

Versions and options

  • SMS or MMS
  • CSView and BMS integration
CLEANSOURCE® XT

Service

Operation and maintenance

Like the rest of the CleanSource family: annual check-up and bearing changes at fixed intervals.

A rotary plant should always be load-tested at commissioning – stepped load, utility failures and transfer to engine.

Load bank test

Other models from Piller

Read more at Bluecircle

Norwerk’s partner Bluecircle has in-depth pages on the topic.

Do you have a project or a system that needs service?

Send us the load, required autonomy and voltage level – or describe the task. We will come back with a solution sized for your operation.

+45 50 53 13 17kontakt@norwerk.dkGet a quote