UNIBLOCK™ UB-V Series
Piller · Rotary UPS (electrically coupled)

Piller UNIBLOCK™ UB-V Series

UB-V is Piller's latest UNIBLOCK™ platform: an electrically coupled UPS where the energy store connects to the UPS unit electrically only. It is built for large data centres and industry and delivers up to 3.24 MW in a single module, reducing the need for many parallel modules.

1.0–3.24 MW / 1.1–3.6 MVApower
Up to 100 MW / 115 MVAparallel
Up to 98 % at 100 % load, 97 % at 50 % (IEC 62040-3)efficiency
Battery or kineticenergy store
  • Hyperscale, colocation and large enterprise data centres
  • Semiconductor production, hospitals, airports and energy
  • Stabilising gas/diesel gensets and gas turbines
Price on requestRange: 1.0–3.24 MW (1.1–3.6 MVA) per unit

Technical data

ManufacturerPiller
TypeRotary UPS (electrically coupled)
Power1.0–3.24 MW / 1.1–3.6 MVA
ParallelUp to 100 MW / 115 MVA
EfficiencyUp to 98 % at 100 % load, 97 % at 50 % (IEC 62040-3)
Energy storeBattery or kinetic
VoltageLow and medium voltage
Voltage dipsCompensates voltage dips up to −50 % without stored energy

Source: www.piller.com; www.piller.com.

Technology

How it works

An all-new electronics platform with self-diagnostics and a real-time Ethernet protocol (PillerLINK™) in a patented ring topology provides redundancy between boards powered from redundant sources.

The unit has no power capacitors or electric fans. On that basis Piller states a mean time between failures up to five times higher than a typical static UPS.

Bi-directional power flow allows energy to be fed back to the grid or moved between sources within a micro-grid.

UNIBLOCK™ UB-V Series

Application

Where it fits

  • Hyperscale, colocation and large enterprise data centres
  • Semiconductor production, hospitals, airports and energy
  • Stabilising gas/diesel gensets and gas turbines
  • Sites exporting embedded generation

Versions and options

  • Containerised plug-and-play version
  • e-VENTLOG™ / Unity Service Pack with remote monitoring
  • Low or medium voltage
UNIBLOCK™ UB-V Series

Service

Operation and maintenance

With remote monitoring and condition-based service, Piller states that off-line service can be as infrequent as every five years, and that e-VENTLOG™ can remove the need for an operational shutdown for up to five years in controlled environments.

A rotary plant should always be load-tested at commissioning – stepped load, utility failures and transfer to engine.

Load bank test

Other models from Piller

Read more at Bluecircle

Norwerk’s partner Bluecircle has in-depth pages on the topic.